MAX15303 PMBus Command Set User’s Guide
Page 26 of 52
VIN_UV_FAULT_RESPONSE
corresponds to a multiple of 100ms, up to a possible maximum of 111
bin
= 700ms. A value of 000
bin
will cause the MAX15303 to use the minimum possible timing value, typically about 30-40ms. (The
default timing for input undervoltage faults is 000